    Brand Name : GINRI
    Model Number : DVRD
    Certification : CE
    Payment Terms : L/C, T/T, Western Union,paypal
    Supply Ability : 20000Pcs per month
    Delivery Time : 5-8 working days
    • Product Details
    • Company Profile

    DC Voltage Controlled 3 Phase Protection Relay 12V 24V 36V 48V High Low Voltage Monitor

    GINRI Voltage Monitoring Relay DC Over/Under Voltage Relay DVRD


    Features:

    • Compact modular size
    • DC circuit monitoring of over-and undervoltage
    • Adjustable over-and undervoltage threshold
    • Adjustable trip delay time
    • Powered by the measuring circuit
    • 2C/O contacts
    • 2 LEDs for status indication

    Protective Functions

    • DC overvoltage
    • DC undervoltage

    Applications

    • DC cabinet
    • Battery
    • Electric control system

    ModelDVRD
    Input circiut =measuring circuitDC supply
    Rated voltageDC12V.DC24V.DC36V,DC48V
    Monitoring functionsOvervoltage,undervoltage
    Voltage setting range
    Rated voltageundervoltageovervolatge
    DC12V10-14V13-17V
    DC24V20-28V26-34V
    DC38V30-42V39-51V
    DC48V40-56V52-68V

    Tripping delay time0.1~15s adjustable
    Voltage hysteresis3-5% fixed
    Reset delay time100ms
    indicatorsnormal,trip
    Output contacts2C/O
    Contact capacity6A,250VAC/30VDC(resistive load)
    Degree of protectionIP20
    Working conditions-25℃~65℃,≤85%RH,non-condensing

    Mechanical

    durability

    1000000 cycles
    Dielectric strength>2KVAC 1min
    Weight130g
    Dimension(HXWXD)79X23X79mm
    MountingDin rail

    For all electrical equipment, there is a rated voltage, but in practice, it is not guaranteed to work at rated voltage, it is a range around the rated voltage, generally required to be ±15%. In order to protect the electrical equipment and process quality, if it is higher than +15%, it is "overvoltage" and the protection action cuts off the power supply.


    Principle of overvoltage protector
    The simplest is to connect a "varistor" in parallel with the power supply line. When the voltage is overvoltage, the varistor breaks down, so that the front end is open or safe, and the back end is out of overvoltage. Disadvantage: varistor overvoltage Need to be replaced after breakdown.